A bill is not set by energy alone. On general and industrial contracts the month's maximum demand sets the basic fee. Cutting the peak by one kilowatt lowers the fee for twelve straight months, so a single adjustment pays for a year.

How the fee works

General (Gap) low voltage charges 6,160 KRW per kW. A 10 kW site pays 61,600 a month, 739,200 a year. On time-of-use contracts the fee follows the larger of the mid-peak and peak maximum demands, so load moved into off-peak drops out of the basis.

A site using 8 kW at 3 p.m. and 6 kW at 10 a.m. is charged on 8 kW. Moving 2 kW from the afternoon to the morning lowers the maximum to 6 kW and the fee by 12,320 a month, 147,840 a year.

Contracted demandMonthly feeAnnual fee
5 kW30,800369,600
10 kW61,600739,200
20 kW123,2001,478,400
50 kW308,0003,696,000

A battery discharges during the peak and lowers the maximum. A 10 kW load held for half an hour with a 5 kW battery supplying half leaves a 5 kW maximum. The saving is 5 × 6,160 × 12 = 369,600 KRW, plus the energy arbitrage.

Load shifting in practice

Shaving does not need a battery. Compressors, chillers, furnaces and washing machines can move to off-peak or mid-peak. Production schedules and working hours are the constraint, so check process by process what can move.

Demand is measured over 15 or 30 minutes, so a momentary dip does nothing; the whole window has to fall. That is why battery controllers monitor the load and discharge automatically.

In a house

The residential progressive tariff has no demand charge. The basic fee is fixed at 910, 1,600 or 7,300 KRW by the tier reached, so shaving a peak does not lower it. Demand management only matters for Jeju households on time-of-use or for a dedicated heat-pump meter.

For a house, the equivalent is staying below the tier boundary. Keeping under 400 kWh saves the 5,700 KRW basic step, and staying under 1,000 kWh in winter avoids 736.2 KRW per kWh. The monthly table shows which month crosses.

How demand is measured

Maximum demand is the highest 15- or 30-minute average in the month. One peak sets the basic fee for twelve months, which is why the peak window deserves attention.

Peaks usually fall between 10 a.m. and noon and between 3 and 6 p.m., depending on the season and the business. Staggering start-up of cooling, heating and production equipment can cut the peak by 10–20% at no cost.

Battery control

Shaving with a battery needs a controller that watches the load and discharges in real time. A timer alone discharges on days with no load and saves nothing. The controller costs money but can be recovered from the demand charge.

Size the battery for 30–50% of the peak. A 5 kWh unit covers half of a 10 kW peak for half an hour; an hour-long peak needs 10 kWh. Measure the duration before choosing.

Adjusting contracted demand

When contracted demand exceeds the actual maximum, the basic fee is wasted: a 15 kW contract with a 10 kW peak pays for 5 kW it never uses. KEPCO will reduce the contract on application.

Cutting too far brings penalties for exceeding the contract. Check the last twelve months of maximum demand and leave 10–20% headroom; a battery allows a lower contract.

Battery and contract demand

A battery lets the contracted demand fall. A site peaking at 10 kW with a 5 kW battery can contract 5 kW, halving the basic fee while the battery covers the peak. Leave headroom for a battery failure, because exceeding the contract carries a penalty, and a reduction is hard to reverse for a year.

The fee is the 2026 general (Gap) low-voltage rate. Contract class and voltage change it, and the actual maximum demand comes from the meter.

Questions

Do homes have a demand charge?

Not on the progressive tariff. Only Jeju time-of-use or general-purpose contracts do.

How much does a battery save on demand?

73,920 KRW per kW a year on general (Gap) low voltage, plus the energy arbitrage. Five kilowatts held for five years is 1.84m.

Which loads should move?

Cooling, compression and furnaces that can store heat or shift time. Lighting and office equipment make little difference.

Price your demand reduction from contracted demand.